This is completed downloadable of Electric Power Distribution Engineering 3rd Gonen Solution Manual
Product Details:
- ISBN-10 : 1482207001
- ISBN-13 : 978-1482207002
- Author: Turan Gönen
A quick scan of any bookstore, library, or online bookseller will produce a multitude of books covering power systems. However, few, if any, are totally devoted to power distribution engineering, and none of them are true textbooks. Filling this vacuum in the power system engineering literature, Electric Power Distribution System Engineering broke new ground.
Written in the classic, self-learning style of the original, Electric Power Distribution Engineering, Third Edition is updated and expanded with:
- Over 180 detailed numerical examples
- More than 170 end-of-chapter problems
- New MATLAB® applications
The Third Edition also features new chapters on:
- Distributed generation
- Renewable energy (e.g., wind and solar energies)
- Modern energy storage systems
- Smart grids and their applications
Designed specifically for junior- or senior-level electrical engineering courses, the book covers all aspects of distribution engineering from basic system planning and concepts through distribution system protection and reliability. Drawing on decades of experience to provide a text that is as attractive to students as it is useful to professors and practicing engineers, the author demonstrates how to design, analyze, and perform modern distribution system engineering. He takes special care to cover industry terms and symbols, providing a glossary and clearly defining each term when it is introduced. The discussion of distribution planning and design considerations goes beyond the usual analytical and qualitative analysis to emphasize the economical explication and overall impact of the distribution design considerations discussed.
Table of Content:
- 1 Distribution System Planning and Automation
- 1.1 INTRODUCTION
- 1.2 DISTRIBUTION SYSTEM PLANNING
- FIGURE 1.1 Typical investment trends in electric utility plants in service.
- FIGURE 1.2 Typical trends in electric utility plants in service by percent of sector.
- FIGURE 1.3 Typical ratio of maintenance expenses to plant in service for each utility sector. The data are for privately owned class A and class B electric utilities.
- 1.3 FACTORS AFFECTING SYSTEM PLANNING
- 1.3.1 Load Forecasting
- FIGURE 1.4 Factors affecting load forecast.
- 1.3.2 Substation Expansion
- FIGURE 1.5 Factors affecting substation expansion.
- 1.3.3 Substation Site Selection
- FIGURE 1.6 Factors affecting substation siting.
- FIGURE 1.7 Substation site selection procedure.
- 1.3.4 Other Factors
- FIGURE 1.8 Factors affecting total cost of the distribution system expansion.
- 1.4 PRESENT DISTRIBUTION SYSTEM PLANNING TECHNIQUES
- FIGURE 1.9 A block diagram of a typical distribution system planning process.
- 1.5 DISTRIBUTION SYSTEM PLANNING MODELS
- 1.5.1 Computer Applications
- 1.5.2 New Expansion Planning
- 1.5.3 Augmentation and Upgrades
- 1.5.4 Operational Planning
- 1.5.5 Benefits of Optimization Applications
- 1.6 DISTRIBUTION SYSTEM PLANNING IN THE FUTURE
- 1.6.1 Economic Factors
- 1.6.2 Demographic Factors
- 1.6.3 Technological Factors
- 1.7 FUTURE NATURE OF DISTRIBUTION PLANNING
- 1.7.1 Increasing Importance of Good Planning
- 1.7.2 Impacts of Load Management (or Demand-Side Management)
- 1.7.3 Cost/Benefit Ratio for Innovation
- 1.7.4 New Planning Tools
- 1.8 CENTRAL ROLE OF THE COMPUTER IN DISTRIBUTION PLANNING
- 1.8.1 System Approach
- 1.8.2 Database Concept
- FIGURE 1.10 A schematic view of a distribution planning system.
- 1.8.3 New Automated Tools
- 1.9 IMPACT OF DISPERSED STORAGE AND GENERATION
- 1.10 DISTRIBUTION SYSTEM AUTOMATION
- TABLE 1.1 Comparison of DSG Devices
- TABLE 1.2 Interaction between DSG Factors and Energy Management System Functions
- TABLE 1.3 Profile of the Electric Utility Industry in the United States in the Year 2000
- FIGURE 1.11 In the future, small dispersed-energy-storage-and-generation units attached to a customer’s home, a power distribution feeder, or a substation would require an increasing amount of automation and control.
- FIGURE 1.12 Monitoring and controlling of an electric power system.
- 1.10.1 Distribution Automation and Control Functions
- TABLE 1.4 Automated Distribution Functions Correlated with Locations
- 1.10.2 Level of Penetration of Distribution Automation
- TABLE 1.5 Functional Scope of Power Distribution Automation System
- FIGURE 1.13 Applications of two-way radio communications.
- FIGURE 1.14 The research system consisted of two minicomputers with distributed high-speed data acquisition processing units at the La Grange Park Substation.
- FIGURE 1.15 Substation control and protection system that features a common signal bus (center lines) to control recording, comparison, and follow-up actions (right). Critical processes are shaded.
- FIGURE 1.16 The integrated distribution control and protection system of EPRI.
- 1.10.3 Alternatives of Communication Systems
- TABLE 1.6 Summary of Advantages and Disadvantages of the Power-Line, Radio, and Telephone Carriers
- FIGURE 1.17 A control hierarchy envisaged for future utilities.
- 1.11 SUMMARY AND CONCLUSIONS
- REFERENCES
- 2 Load Characteristics
- 2.1 BASIC DEFINITIONS
- Example 2.1
- FIGURE 2.1 A daily demand variation curve.
- FIGURE 2.2 A load duration curve.
- TABLE 2.1 Idealized Load Data for the NL&NP’s Primary Feeder
- FIGURE 2.3 The daily load curve for Example 2.1.
- FIGURE 2.4 Development of aggregate load curves for winter peak period. Miscellaneous load includes street lighting and sales to other agencies. Dashed curve shown on system load diagram is actual system generation sent out. Solid curve is based on group load study data.
- Example 2.2
- Example 2.3
- FIGURE 2.5 Illustration of load connected to a distribution transformer.
- Example 2.4
- Example 2.5
- FIGURE 2.6 NL&NP’s riverside distribution substation.
- FIGURE 2.7 Daily load curves of a substation transformer.
- Example 2.6
- 2.2 RELATIONSHIP BETWEEN THE LOAD AND LOSS FACTORS
- FIGURE 2.8 A feeder with a variable load.
- FIGURE 2.9 An arbitrary and ideal load curve.
- FIGURE 2.10 Loss factor curves as a function of load factor.
- Example 2.7
- Example 2.8
- FIGURE 2.11 A monthly load curve.
- Example 2.9
- FIGURE 2.12 The new load curve after the new load addition.
- Example 2.10
- Example 2.11
- 2.3 MAXIMUM DIVERSIFIED DEMAND
- Example 2.12
- TABLE 2.2 Hourly Variation Factors
- FIGURE 2.13 Maximum diversified 30 min demand characteristics of various residential loads: A, clothes dryer; B, off-peak water heater, “off-peak” load; C, water heater, uncontrolled, interlocked elements; D, range; E, lighting and miscellaneous appliances; F, 0.5-hp room coolers; G, off-peak water heater, “on-peak” load, upper element uncontrolled; H, oil burner; I, home freezer; J, refrigerator; K, central air-conditioning, including heat-pump cooling, 5-hp heat pump (4-ton air conditioner); L, house heating, including heat-pump-heating-connected load of 15 kW unit-type resistance heating or 5 hp heat pump.
- 2.4 LOAD FORECASTING
- TABLE 2.3 MATLAB® Demand-Forecasting Computer Program
- 2.4.1 Box—Jenkins Methodology
- 2.4.2 Small-Area Load Forecasting
- 2.4.3 Spatial Load Forecasting
- FIGURE 2.14 Spatial load forecasting.
- Example 2.13
- TABLE 2.4 Demand Forecasting MATLAB Program
- Example 2.14
- FIGURE 2.15 The answers for the parts (a) and (b).
- 2.5 LOAD MANAGEMENT
- Example 2.15
- 2.6 RATE STRUCTURE
- 2.6.1 Customer Billing
- FIGURE 2.16 A customer’s monthly electric bill.
- TABLE 2.5 Typical Energy Rate Schedule for Commercial Users
- 2.6.2 Fuel Cost Adjustment
- Example 2.16
- FIGURE 2.17 Two customers connected to a primary line of the NL&NP.
- 2.7 ELECTRIC METER TYPES
- FIGURE 2.18 Single-phase electromechanical watthour meter.
- FIGURE 2.19 Basic parts of a single-phase electromechanical watthour meter.
- FIGURE 2.20 Diagram of a typical motor and magnetic retarding system for a single-phase electromechanical watthour meter.
- FIGURE 2.21 Typical polyphase (electromechanical) watthour meters: (a) self-contained meter (socket-connected cyclometer type). (b) transformer-rated meter (bottom-connected pointer type).
- FIGURE 2.22 Single-phase, two-wire electromechanical watthour meter connected to a high-voltage circuit through current and potential transformers.
- FIGURE 2.23 The register of an electromechanical demand meter for large customers.
- 2.7.1 Electronic (or Digital) Meters
- 2.7.2 Reading Electric Meters
- FIGURE 2.24 A conventional dial-type register of electromechanical meter.
- FIGURE 2.25 A cyclometer-type register.
- 2.7.3 Instantaneous Load Measurements Using Electromechanical Watthour Meters
- Example 2.17
- Example 2.18
- Example 2.19
- PROBLEMS
- TABLE P.2.1 Typical Summer-Day Load, in kW
- REFERENCES
- 3 Application of Distribution Transformers
- 3.1 INTRODUCTION
- TABLE 3.1 Standard Transformer Kilovoltamperes and Voltages
- TABLE 3.2 Designation of Voltage Ratings for Single- and Three-Phase Distribution Transformers
- 3.2 TYPES OF DISTRIBUTION TRANSFORMERS
- FIGURE 3.1 Overhead pole-mounted distribution transformers: (a) single-phase completely self-protecting (or conventional) and (b) three phase.
- FIGURE 3.2 Network transformer.
- FIGURE 3.3 Dry-type pole-mounted resibloc transformer.
- FIGURE 3.4 Dry-type resibloc network transformer.
- FIGURE 3.5 Outdoor three-phase dry-type resibloc transformer.
- FIGURE 3.6 Pad-mount-type single-phase resibloc transformer.
- FIGURE 3.7 Pad-mount three-phase resibloc transformer.
- FIGURE 3.8 An arch flash-resistant dry-type three-phase resibloc transformer.
- FIGURE 3.9 TRIDRY dry-type resibloc transformer.
- FIGURE 3.10 VPI dry resibloc transformer.
- FIGURE 3.11 Pad-mount installation of three-phase resibloc transformer.
- FIGURE 3.12 Various types of transformer: (a) a typical secondary unit substation transformer, (b) a typical single-phase pole-type tansformer, (c) a single-phase pad-mounted transformer, and (d) three-phase pad-mounted transformer.
- FIGURE 3.13 Various types of transformers: (a) three-phase sub-surface-vault type transformer, (b) a typical mobile transformer, and (c) a typical power transformer.
- TABLE 3.3 Electrical Characteristics of Typical Single-Phase Distribution Transformers
- TABLE 3.4 Electrical Characteristics of Typical Three-Phase Pad-Mounted Transformers
- 3.3 REGULATION
- 3.4 TRANSFORMER EFFICIENCY
- FIGURE 3.14 Transformer efficiency chart applicable only to the unity PF condition. To obtain the efficiency at a given load, lay a straightedge across the iron and copper loss values and read the efficiency at the point where the straightedge cuts the required load ordinate.
- 3.5 TERMINAL OR LEAD MARKINGS
- FIGURE 3.15 Transformer efficiency chart applicable only to the unity PF condition. To obtain the efficiency at a given load, lay a straightedge across the iron and copper loss values and read the efficiency at the point where the straightedge cuts the required load ordinate.
- FIGURE 3.16 Cost of electric energy.
- FIGURE 3.17 Annual cost per unit load vs. load level.
- 3.6 TRANSFORMER POLARITY
- FIGURE 3.18 Additive and subtractive polarity connections: (a) subtractive polarity and (b) additive polarity.
- FIGURE 3.19 Polarity test: (a) subtractive polarity and (b) additive polarity.
- 3.7 DISTRIBUTION TRANSFORMER LOADING GUIDES
- 3.8 EQUIVALENT CIRCUITS OF A TRANSFORMER
- FIGURE 3.20 Basic circuit of a practical transformer.
- FIGURE 3.21 Equivalent circuit of a loaded transformer.
- FIGURE 3.22 Phasor diagram corresponding to the excitation current components at no load.
- FIGURE 3.23 Equivalent circuit with the referred secondary values.
- FIGURE 3.24 Simplified equivalent circuit assuming negligible excitation current.
- FIGURE 3.25 Simplified equivalent circuit for a large-sized power transformer.
- 3.9 SINGLE-PHASE TRANSFORMER CONNECTIONS
- 3.9.1 General
- FIGURE 3.26 Single-phase transformer connections.
- FIGURE 3.27 Single-phase transformer connections.
- 3.9.2 Single-Phase Transformer Paralleling
- FIGURE 3.28 Single-phase transformer paralleling.
- FIGURE 3.29 Parallel operation of two single-phase transformers.
- FIGURE 3.30 Two transformers connected in parallel and feeding a load.
- FIGURE 3.31 Equivalent circuit.
- Example 3.1
- FIGURE 3.32 An equivalent circuit of a single-phase transformer with three-wire secondary.
- Example 3.2
- FIGURE 3.33 Secondary line-to-neutral fault.
- FIGURE 3.34 Secondary line-to-line fault.
- Example 3.3
- Example 3.4
- 3.10 THREE-PHASE CONNECTIONS
- 3.10.1 Δ–Δ Transformer Connection
- FIGURE 3.35 Eco-dry three-phase (RESIBLOC) transformer.
- FIGURE 3.36 Air-to-water cooled RESIBLOC three-phase transformer.
- FIGURE 3.37 Eco-dry (RESIBLOC) three-phase transformer.
- FIGURE 3.38 Vacuum cast dry-type transformer.
- FIGURE 3.39 Δ–Δ transformer bank connection with 0° angular displacement.
- FIGURE 3.40 Δ–Δ transformer bank connection with 180° angular displacement.
- FIGURE 3.41 Δ–Δ transformer bank connection to provide 120/208/240 V three-phase four-wire service.
- TABLE 3.5 Permissible Percent Loading on Odd and Like Transformers as a Function of the Z1/Z2 Ratio
- FIGURE 3.42 Equivalent circuit of a Δ–Δ-connected transformer bank.
- Example 3.5
- FIGURE 3.43 For Example 3.5.
- 3.10.2 Open-Δ Open-Δ Transformer Connection
- FIGURE 3.44 Three-phase four-wire open-delta connection.
- FIGURE 3.45 Three-phase three-wire open-delta connection.
- TABLE 3.6 Effects of the Load Power Factor on the Transformer Power Factors
- 3.10.3 Y–Y Transformer Connection
- FIGURE 3.46 Y–Y connection to provide a 120/208 V grounded-wye three-phase four-wire multigrounded service.
- 3.10.4 Y–Δ Transformer Connection
- FIGURE 3.47 Y–Δ connection to provide a 120/208/240 V three-phase four-wire secondary service.
- FIGURE 3.48 Y–Δ connection to provide a 240 V three-phase three-wire secondary service.
- 3.10.5 Open-Y Open-Δ Transformer Connection
- Example 3.6
- FIGURE 3.49 Open-wye open-delta connection.
- FIGURE 3.50 Open-wye open-delta connection for Example 3.6.
- 3.10.6 Δ–Y Transformer Connection
- FIGURE 3.51 Δ–Y connection with 30° angular displacement.
- FIGURE 3.52 Δ–Y connection with 210° angular displacement.
- 3.11 THREE-PHASE TRANSFORMERS
- FIGURE 3.53 Three-phase transformer connected in delta–delta.
- FIGURE 3.54 Three-phase transformer connected in open-delta.
- FIGURE 3.55 Three-phase transformer connected in Y–Δ.
- FIGURE 3.56 Three-phase transformer connected in open-wye open-delta.
- FIGURE 3.57 Three-phase transformer connected in Y–Y.
- 3.12 T OR SCOTT CONNECTION
- FIGURE 3.58 T or Scott connection for three-phase to two-phase, three-wire transformation.
- FIGURE 3.59 T or Scott connection for three-phase to two-phase, four-wire transformation.
- FIGURE 3.60 T or Scott connection for three-phase to two-phase, five-wire transformation.
- Example 3.7
- FIGURE 3.61 For Example 3.7.
- FIGURE 3.62 For Example 3.7.
- Example 3.8
- FIGURE 3.63 A particular T–T connection.
- FIGURE 3.64 The required low-voltage phasor diagram.
- Example 3.9
- FIGURE 3.65 Phasor diagram for Example 3.9.
- Example 3.10
- Example 3.11
- FIGURE 3.66 Two single-phase transformers connected in open-wye and open-delta.
- FIGURE 3.67 The low-voltage phasor diagram for Example 3.11.
- 3.13 AUTOTRANSFORMER
- FIGURE 3.68 Wiring diagram of a single-phase autotransformer.
- FIGURE 3.69 Single-phase autotransformer.
- FIGURE 3.70 Three-phase autotransformer.
- 3.14 BOOSTER TRANSFORMERS
- FIGURE 3.71 Single-phase booster transformer connection: (a) for 5% boost and (b) for 10% boost.
- FIGURE 3.72 Three-phase three-wire booster transformer connection using two single-phase booster transformers.
- 3.15 AMORPHOUS METAL DISTRIBUTION TRANSFORMERS
- FIGURE 3.73 Three-phase three-wire booster transformer connection using three single-phase booster transformers.
- 3.16 NATURE OF ZERO-SEQUENCE CURRENTS
- FIGURE 3.74 A three-phase system: (a) with four wires and wye-connected load and (b) three wires and wye- or delta-connected load.
- FIGURE 3.75 For Example 3.12.
- Example 3.12
- FIGURE 3.76 Solutions for Example 3.12.
- Example 3.13
- FIGURE 3.77 Three-phase transformer connection for Example 3.12.
- FIGURE 3.78 The answers for Example 3.12.
- FIGURE 3.79 Δ–Y transformer bank connections for Example 3.13.
- Example 3.14
- Example 3.15
- FIGURE 3.80 Solutions for Example 3.13.
- Example 3.16
- FIGURE 3.81 Three-phase transformer connections for Example 3.12.
- 3.17 ZIGZAG POWER TRANSFORMERS
- FIGURE 3.82 The answers for Example 3.12.
- FIGURE 3.83 Three-phase transformer connections for Example 3.16.
- FIGURE 3.84 Solutions for Example 3.16.
- 3.18 GROUNDING TRANSFORMERS USED IN THE UTILITY SYSTEMS
- FIGURE 3.85 Two different ways of connecting a grounding transformer to the system.
- FIGURE 3.86 A Y–Δ transformer can also be used as a grounding transformer.
- FIGURE 3.87 (a through d) A zigzag transformer is often used to obtain a neutral for the grounding of a Δ–Δ connected system.
- 3.19 PROTECTION SCHEME OF A DISTRIBUTION FEEDER CIRCUIT
- FIGURE 3.88 A distribution feeder protection scheme.
- PROBLEMS
- FIGURE P3.1 For Problem 3.1.
- FIGURE P3.3 A T–T connection.
- FIGURE P3.6 For Problem 3.6.
- FIGURE P3.7 For Problem 3.7.
- FIGURE P3.8 For Problem 3.8.
- REFERENCES
- 4 Design of Subtransmission Lines and Distribution Substations
- 4.1 INTRODUCTION
- FIGURE 4.1 One-line diagram of a typical distribution system.
- 4.2 SUBTRANSMISSION
- FIGURE 4.2 Radial-type subtransmission.
- FIGURE 4.3 Improved form of radial-type subtransmission.
- FIGURE 4.4 Loop-type subtransmission.
- FIGURE 4.5 Grid- or network-type subtransmission.
- 4.2.1 Subtransmission Line Costs
- 4.3 DISTRIBUTION SUBSTATIONS
- FIGURE 4.6 A typical distribution substation.
- FIGURE 4.7 A typical small distribution substation.
- FIGURE 4.8 Overview of a modern substation.
- FIGURE 4.9 Close view of typical modern distribution substation transformer.
- FIGURE 4.10 Primary unit substation transformer.
- FIGURE 4.11 Secondary unit substation transformer.
- FIGURE 4.12 A 630 kVA, 10/0.4 kV GEAFOL solid dielectric transformer.
- FIGURE 4.13 Oil distribution transformer: cutaway of a TUMERIC transformer with an oil expansion tank showing in the foreground and TUNORMA with an oil expansion tank shown in the background.
- FIGURE 4.14 A 630 kVA, 10/0.4 kV GEAFOL solid dielectric transformer.
- FIGURE 4.15 A 40 MVA, 110 kV ± 16%/21 kV, three-phase, core-type transformer, 5.2 m high, 9.4 m long, 3 m wide, and weighing 80 tons.
- 4.3.1 Substation Costs
- FIGURE 4.16 A850/950/1100 MVA, 415 kV ± 11%/27 kV, three-phase, shell-type transformer, 11.3 m high, 14 m long, 5.7 m wide, and weighing (without cooling oil) 552 tons.
- FIGURE 4.17 A completely assembled 910 MVA, 20.5/500 kV, three-phase, step-up transformer, about 12 m high, 11 m long, 9 m wide, and weighing 562 tons.
- FIGURE 4.18 A typical core and coil assembly of a three-phase, core-type, power transformer.
- Example 4.1
- 4.4 SUBSTATION BUS SCHEMES
- 4.5 SUBSTATION LOCATION
- FIGURE 4.19 A typical single bus scheme.
- FIGURE 4.20 A typical double bus–double breaker scheme.
- FIGURE 4.21 A typical main-and-transfer bus scheme.
- FIGURE 4.22 A typical double bus–single breaker scheme.
- FIGURE 4.23 A typical ring bus scheme.
- FIGURE 4.24 A typical breaker-and-a-half scheme.
- 4.6 RATING OF A DISTRIBUTION SUBSTATION
- TABLE 4.1 Summary of Comparison of Switching Schemesa
- FIGURE 4.25 Square-shaped distribution substation service area.
- FIGURE 4.26 The K constant for copper conductors, assuming a lagging-load power factor of 0.9.
- FIGURE 4.27 Hexagonally shaped distribution substation area.
- 4.7 GENERAL CASE: SUBSTATION SERVICE AREA WITH n PRIMARY FEEDERS
- FIGURE 4.28 Distribution substation service area served by n primary feeders.
- TABLE 4.2 Application Results of Equation 4.17
- 4.8 COMPARISON OF THE FOUR- AND SIX-FEEDER PATTERNS
- 4.9 DERIVATION OF THE K CONSTANT
- FIGURE 4.29 An illustration of a primary-feeder main.
- FIGURE 4.30 Phasor diagram.
- Example 4.2
- Example 4.3
- Example 4.4
- FIGURE 4.31 The feeder of Example 4.2.
- FIGURE 4.32 The feeder of Example 4.4.
- Example 4.5
- FIGURE 4.33 The feeder of Example 4.5.
- Example 4.6
- 4.10 SUBSTATION APPLICATION CURVES
- FIGURE 4.34 Distribution substation application curves for 3% voltage drop.
- FIGURE 4.35 Distribution substation application curves for 6% voltage drop.
- Example 4.7
- TABLE 4.3 Data for Example 4.7
- TABLE 4.4 Cases of Example 4.7
- 4.11 INTERPRETATION OF PERCENT VOLTAGE DROP FORMULA
- TABLE 4.5 Illustration of the Use and Interpretation of Equation 4.85
- Example 4.8
- Example 4.9
- FIGURE 4.36 For Example 4.9.
- Example 4.10
- FIGURE 4.37 Service area for Example 4.10.
- Example 4.11
- FIGURE 4.38 Service area for Example 4.11.
- FIGURE 4.39 Linearly decreasing load for Example 4.11.
- Example 4.12
- 4.12 CAPABILITY OF FACILITIES
- 4.13 SUBSTATION GROUNDING
- 4.13.1 Electric Shock and Its Effects on Humans
- TABLE 4.6 Effect of Electric Current (mA) on Men and Women
- TABLE 4.7 Resistivity of Different Soils
- Example 4.13
- 4.13.2 Ground Resistance
- TABLE 4.8 Resistivity of Different Soils
- TABLE 4.9 Effect of Moisture Content on Soil Resistivity
- FIGURE 4.40 Typical electric shock hazard situations: (a) touch potential; (b) its equivalent circuit; (c) step potential; (d) its equivalent circuit.
- FIGURE 4.41 Possible basic shock situations.
- 4.13.3 Reduction of Factor Cs
- FIGURE 4.42 Surface layer derating factor Cs versus thickness of surface material in m.
- Example 4.14
- FIGURE 4.43 Resistance of earth surrounding an electrode.
- FIGURE 4.44 Variation of soil resistivity with depth for soil having uniform moisture content at all depths.
- 4.13.4 Soil Resistivity Measurements
- 4.13.4.1 Wenner Four-Pin Method
- FIGURE 4.45 Approximate ground resistivity distribution in the United States.
- FIGURE 4.46 The Wenner four-pin method.
- 4.13.4.2 Three-Pin or Driven Ground Rod Method
- FIGURE 4.47 Circuit diagram for three-pin or driven ground rod method.
- 4.14 SUBSTATION GROUNDING
- FIGURE 4.48 The relationship between asymmetrical fault current, dc decaying component, and symmetrical fault current.
- 4.15 GROUND CONDUCTOR SIZING FACTORS
- TABLE 4.10 Material Constants of the Typical Grounding Material Used
- 4.16 MESH VOLTAGE DESIGN CALCULATIONS
- FIGURE 4.49 The effect of the spacing (D) between conductors on Km.
- FIGURE 4.50 The effect of the number of conductors (n) on the Km.
- FIGURE 4.51 The relationship between the diameter of the conductor (d) and the Km.
- FIGURE 4.52 The relationship between the depth of the conductor (h) and Km.
- 4.17 STEP VOLTAGE DESIGN CALCULATIONS
- FIGURE 4.53 The relationship between the distance (D) between the conductors and the geometric factor Ks.
- FIGURE 4.54 The relationship between the number of conductors (n) and the geometric factor Ks.
- FIGURE 4.55 The relationship between the depth of grid conductors (h) in meter and the geometric factor Ks.
- 4.18 TYPES OF GROUND FAULTS
- 4.18.1 Line-to-Line-to-Ground Fault
- 4.18.2 Single Line-to-Ground Fault
- 4.19 GROUND POTENTIAL RISE
- FIGURE 4.56 The effects of the number of grid conductors (n), without ground rods, on the ground grid resistance.
- Example 4.15
- FIGURE 4.57 The effects of varying the depth of burial of the grid (h) from 0.5 to 2.5 m and the number of conductors from 4 to 10[17].
- FIGURE 4.58 Substation grounding design procedure block diagram.
- TABLE 4.11 Initial Design Parameters
- TABLE 4.12 Approximate Equivalent Impedance of Transmission Line Overhead Shield Wires and Distribution Feeder Neutrals
- 4.20 TRANSMISSION LINE GROUNDS
- FIGURE 4.59 Two basic types of counterpoises: (a) continuous (parallel) and (b) radial.
- 4.21 TYPES OF GROUNDING
- FIGURE 4.60 Grounding transformers used in delta-connected systems: (a) using grounded wye–delta-connected small distribution transformers or (b) using grounding autotransformers with interconnected wye or “zigzag” windings.
- 4.22 TRANSFORMER CLASSIFICATIONS
- TABLE 4.13 Equivalent Cooling Classes
- PROBLEMS
- REFERENCES
- 5 Design Considerations of Primary Systems
- 5.1 INTRODUCTION
- FIGURE 5.1 One-line diagram of typical primary distribution feeders.
- 5.2 RADIAL-TYPE PRIMARY FEEDER
- FIGURE 5.2 Radial-type primary feeder.
- FIGURE 5.3 Radial-type primary feeder with tie and sectionalizing switches.
- 5.3 LOOP-TYPE PRIMARY FEEDER
- FIGURE 5.4 Radial-type primary feeder with express feeder and backfeed.
- FIGURE 5.5 Radial-type phase-area feeder.
- FIGURE 5.6 Loop-type primary feeder.
- 5.4 PRIMARY NETWORK
- FIGURE 5.7 Primary network.
- 5.5 PRIMARY-FEEDER VOLTAGE LEVELS
- FIGURE 5.8 Factors affecting primary-feeder voltage-level selection decision.
- TABLE 5.1 Typical Primary Voltage Levels
- FIGURE 5.9 Illustration of the voltage-square rule and the feeder distance-coverage principle as a function of feeder voltage level and a single load.
- FIGURE 5.10 Feeder area-coverage principle as related to feeder voltage and a uniformly distributed load.
- 5.6 PRIMARY-FEEDER LOADING
- FIGURE 5.11 Factors affecting feeder routing decisions.
- FIGURE 5.12 Factors affecting the number of feeders.
- FIGURE 5.13 Factors affecting conductor size selection.
- 5.7 TIE LINES
- 5.8 DISTRIBUTION FEEDER EXIT: RECTANGULAR-TYPE DEVELOPMENT
- FIGURE 5.14 One-line diagram of typical two-substation area supply with tie lines.
- FIGURE 5.15 Rectangular-type development.
- FIGURE 5.16 Rectangular-type development with two transformers, type 1.
- FIGURE 5.17 Rectangular-type development with two transformers, type 2.
- FIGURE 5.18 Rectangular-type development with three transformers.
- FIGURE 5.19 The sequence of installing additional transformers and feeders, type 1.
- FIGURE 5.20 The sequence of installing additional transformers and feeders, type 2.
- FIGURE 5.21 The sequence of installing additional transformers, type 3.
- FIGURE 5.22 The sequence of installing additional transformers and feeders, type 4.
- FIGURE 5.23 The sequence of installing additional transformers, type 5.
- 5.9 RADIAL-TYPE DEVELOPMENT
- 5.10 RADIAL FEEDERS WITH UNIFORMLY DISTRIBUTED LOAD
- FIGURE 5.24 Radial-type development: (a) type 1, (b) type 2, (c) type 3, and (d) type 4.
- FIGURE 5.25 A radial feeder.
- FIGURE 5.26 A uniformly distributed main feeder.
- 5.11 RADIAL FEEDERS WITH NONUNIFORMLY DISTRIBUTED LOAD
- FIGURE 5.27 A uniformly increasing load.
- FIGURE 5.28 The sending-end current as a function of the distance along a feeder.
- 5.12 APPLICATION OF THE A, B, C, D GENERAL CIRCUIT CONSTANTS TO RADIAL FEEDERS
- FIGURE 5.29 A symbolic representation of a line.
- FIGURE 5.30 Phasor diagram.
- FIGURE 5.31 A radial feeder.
- Example 5.1
- 5.13 DESIGN OF RADIAL PRIMARY DISTRIBUTION SYSTEMS
- 5.13.1 Overhead Primaries
- FIGURE 5.32 An overhead radial distribution system.
- 5.13.2 Underground Residential Distribution
- FIGURE 5.33 A two-way feed-type underground residential distribution system.
- FIGURE 5.34 Single-line diagram of loop-type primary-feeder circuits: (a) with a disconnect switch at each transformer and (b) without a disconnect switch at each transformer.
- FIGURE 5.35 A distribution transformer with internal high-voltage fuse and load-break connectors.
- FIGURE 5.36 A distribution transformer with internal high-voltage fuses and load-break switches.
- Example 5.2
- FIGURE 5.37 The “longest” primary circuit.
- Example 5.3
- TABLE 5.2 Current-Carrying Capacity of XLPE Aerial Cables
- Example 5.4
- Example 5.5
- TABLE 5.3 15 kV Concentric Neutral XLPE-Insulated Al URD Cable
- 5.14 PRIMARY SYSTEM COSTS
- PROBLEMS
- REFERENCES
- 6 Design Considerations of Secondary Systems
- 6.1 INTRODUCTION
- 6.2 SECONDARY VOLTAGE LEVELS
- 6.3 PRESENT DESIGN PRACTICE
- FIGURE 6.1 One-line diagram of a simple radial secondary system.
- 6.4 SECONDARY BANKING
- FIGURE 6.2 Two different methods of banking secondaries: (a) type 1 and (b) type 2.
- FIGURE 6.3 Two additional methods of banking secondaries: (a) type 3 and (b) type 4.
- 6.5 SECONDARY NETWORKS
- FIGURE 6.4 One-line diagram of the small segment of a secondary-network system.
- 6.5.1 Secondary Mains
- 6.5.2 Limiters
- FIGURE 6.5 Limiter characteristics in terms of time to fuse versus current and insulation-damage characteristics of the underground-network cables.
- 6.5.3 Network Protectors
- 6.5.4 High-Voltage Switch
- FIGURE 6.6 An ideal coordination of secondary-network overcurrent protection devices.
- TABLE 6.1 Required Operation of the Protective Apparatus
- 6.5.5 Network Transformers
- FIGURE 6.7 High-voltage switch.
- 6.5.6 Transformer Application Factor
- TABLE 6.2 Standard Ratings for Three-Phase Secondary-Network Transformers Transformer High Voltage
- 6.6 SPOT NETWORKS
- FIGURE 6.8 Network-transformer application factors as a function of ZM/ZT ratio and number of feeders used.
- 6.7 ECONOMIC DESIGN OF SECONDARIES
- 6.7.1 Patterns and Some of the Variables
- FIGURE 6.9 One-line diagram of the multiple primary system for the John Hancock Center.
- FIGURE 6.10 Illustration of a typical pattern.
- 6.7.2 Further Assumptions
- 6.7.3 General TAC Equation
- 6.7.4 Illustrating the Assembly of Cost Data
- 6.7.5 Illustrating the Estimation of Circuit Loading
- TABLE 6.3 Illustrative Load Data
- FIGURE 6.11 Estimated circuit loading for copper-loss determinations.
- 6.7.6 Developed Total Annual Cost Equation
- 6.7.7 Minimization of the Total Annual Costs
- 6.7.8 Other Constraints
- Example 6.1
- FIGURE 6.12 Residential area lot layout and service arrangement.
- FIGURE 6.13 Residential area lot layout and utility easement arrangement.
- TABLE 6.4 Load Data for Example 6.1
- FIGURE 6.14 Illustration of the SLs.
- 6.8 UNBALANCED LOAD AND VOLTAGES
- Example 6.2
- FIGURE 6.15 An unbalanced single-phase three-wire secondary circuit.
- FIGURE 6.16 Vertical spacing between the secondary wires.
- Example 6.3
- Example 6.4
- Example 6.5
- FIGURE 6.17
- TABLE 6.5 Bus Voltage Value (pu)
- 6.9 SECONDARY SYSTEM COSTS
- Example 6.6
- PROBLEMS
- REFERENCES
- 7 Voltage-Drop and Power-Loss Calculations
- 7.1 THREE-PHASE BALANCED PRIMARY LINES
- 7.2 NON-THREE-PHASE PRIMARY LINES
- 7.2.1 Single-Phase Two-Wire Laterals with Ungrounded Neutral
- FIGURE 7.1 Various lateral types that exist in the United States.
- 7.2.2 Single-Phase Two-Wire Ungrounded Laterals
- 7.2.3 Single-Phase Two-Wire Laterals with Multigrounded Common Neutrals
- FIGURE 7.2 A single-phase lateral with multigrounded common neutral.
- 7.2.4 Two-Phase Plus Neutral (Open-Wye) Laterals
- FIGURE 7.3 An open-wye connected lateral.
- Example 7.1
- Example 7.2
- Example 7.3
- 7.3 FOUR-WIRE MULTIGROUNDED COMMON NEUTRAL DISTRIBUTION SYSTEM
- FIGURE 7.4 A four-wire multigrounded common neutral distribution system.
- Example 7.4
- FIGURE 7.5 A single-phase circuit.
- FIGURE 7.6 Impedance triangle.
- Example 7.5
- FIGURE 7.7 One-line diagram of a three-phase four-wire secondary system.
- Example 7.6
- TABLE 7.1 Single-Phase 7200-120/240-V Distribution Transformer Data at 65°C
- FIGURE 7.8 Triplexed cable assembly.
- FIGURE 7.9 Twin concentric cable assembly.
- TABLE 7.2 Twin Concentric Al/Cu XLPE 600 V Cable Data
- TABLE 7.3 Load Data
- Example 7.7
- FIGURE 7.10 Circulation of the secondary-line currents.
- Example 7.8
- FIGURE 7.11 A residential secondary distribution system.
- Example 7.9
- FIGURE 7.12 The distribution system of Example 7.9.
- Example 7.10
- FIGURE 7.13 A square-shaped service area and a lumped-sum load.
- Example 7.11
- Example 7.12
- FIGURE 7.14 The distribution system of Example 7.12.
- Example 7.13
- Example 7.14
- FIGURE 7.15 The distribution system of Example 7.14.
- TABLE 7.4 K Constants
- 7.4 PERCENT POWER (OR COPPER) LOSS
- TABLE 7.5 Conductor I2R Losses, kWh/(mi year), at 7.2/12.5 kV and a Load Factor of 0.6
- 7.5 METHOD TO ANALYZE DISTRIBUTION COSTS
- 7.5.1 Annual Equivalent of Investment Cost
- 7.5.2 Annual Equivalent of Energy Cost
- 7.5.3 Annual Equivalent of Demand Cost
- 7.5.4 Levelized Annual Cost
- FIGURE 7.16 Illustration of the levelized annual cost concept: (a) unlevelized annual cost flow diagram and (b) levelized cost flow diagram.
- Example 7.15
- TABLE 7.6 Typical ACSR Conductors Used in Rural Areas
- TABLE 7.7 Typical ACSR Conductors Used in Urban Areas
- FIGURE 7.17 Total annual equivalent cost of ACSR feeders for rural areas in thousands of dollars per mile: (a) 477 cmil, 26 strands, (b) 266.8 cmil, 6 strands, AWG 4/0, and AWG 3/0.
- Example 7.16
- FIGURE 7.18 Total annual equivalent cost of ACSR feeders for urban areas in thousands of dollars per mile: (a) 477 cmil, 26 strands, (b) AWG 3/0, (c) AWG 1/0, and (d) AWG 4, 7 strands.
- Example 7.17
- 7.6 ECONOMIC ANALYSIS OF EQUIPMENT LOSSES
- PROBLEMS
- FIGURE P7.1 One-line diagram for Problem 7.1.
- FIGURE P7.7 Illustration for Example 7.7.
- FIGURE P7.11 Distribution system for Problem 7.11.
- REFERENCES
- 8 Application of Capacitors to Distribution Systems
- 8.1 BASIC DEFINITIONS
- 8.2 POWER CAPACITORS
- FIGURE 8.1 A cutaway view of a power factor correction capacitor.
- FIGURE 8.2 A typical utilization in a switched pole-top rack.
- 8.3 EFFECTS OF SERIES AND SHUNT CAPACITORS
- 8.3.1 Series Capacitors
- FIGURE 8.3 Voltage phasor diagrams for a feeder circuit of lagging power factor: (a) and (c) without and (b) and (d) with series capacitors.
- 8.3.1.1 Overcompensation
- FIGURE 8.4 Overcompensation of the receiving-end voltage: (a) at normal load and (b) at the start of a large motor.
- FIGURE 8.5 Voltage phasor diagram with leading power factor: (a) without series capacitors and (b) with series capacitors.
- 8.3.1.2 Leading Power Factor
- 8.3.2 Shunt Capacitors
- FIGURE 8.6 Voltage phasor diagrams for a feeder circuit of lagging power factor: (a) and (c) without and (b) and (d) with shunt capacitors.
- Example 8.1
- FIGURE 8.7 (a) Phasor diagram and (b) power triangle for a typical distribution load.
- 8.4 POWER FACTOR CORRECTION
- 8.4.1 General
- FIGURE 8.8 Illustration of (a) the use of a power triangle for power factor correction by employing capacitive reactive power and (b) the required increase in the apparent and reactive powers as a function of the load power factor, holding the real power of the load constant.
- FIGURE 8.9 Illustration of the change in the real and reactive powers as a function of the load power factor, holding the apparent power of the load constant.
- FIGURE 8.10 Illustration of power factor correction.
- 8.4.2 Concept of Leading and Lagging Power Factors
- 8.4.3 Economic Power Factor
- FIGURE 8.11 Examples of some of the sources of leading and lagging reactive power at the load.
- TABLE 8.1 Power Factor of Load and Source
- 8.4.4 Use of a Power Factor Correction Table
- 8.4.5 Alternating Cycles of a Magnetic Field
- 8.4.6 Power Factor of a Group of Loads
- Example 8.2
- TABLE 8.2 Determination of kW Multiplies to Calculate kvar Requirement for Power Factor Correction
- FIGURE 8.12 For Example 8.2: (a) connection diagram, (b) phasor diagrams of individual loads, and (c) phasor diagram of combined loads.
- 8.4.7 Practical Methods Used by the Power Industry for Power Factor Improvement Calculations
- Example 8.3
- FIGURE 8.13 Illustration of power factor correction using a shunt capacitor in Example 8.3.
- Example 8.4
- Example 8.5
- FIGURE 8.14 Component current diagram.
- Example 8.6
- 8.4.8 Real Power-Limited Equipment
- Example 8.7
- Example 8.8
- 8.4.9 Computerized Method to Determine the Economic Power Factor
- 8.5 APPLICATION OF CAPACITORS
- Example 8.9
- FIGURE 8.15 Connection of capacitor units for one phase of a three-phase wye-connected bank.
- FIGURE 8.16 Secondary capacitor economics considering only savings in distribution transformer cost.
- FIGURE 8.17 Capacitor connected (a) in delta and (b) in wye.
- Example 8.10
- Example 8.11
- Example 8.12
- Example 8.13
- 8.5.1 Capacitor Installation Types
- FIGURE 8.18 The effects of a fixed capacitor on the voltage profile of (a) feeder with uniformly distributed load (b) at heavy load and (c) at light load.
- FIGURE 8.19 Sizing of the fixed and switched capacitors to meet the daily reactive power demands.
- 8.5.2 Types of Controls for Switched Shunt Capacitors
- 8.5.3 Types of Three-Phase Capacitor-Bank Connections
- FIGURE 8.20 Meeting the reactive power requirements with fixed, voltage-controlled, and time-controlled capacitors.
- 8.6 ECONOMIC JUSTIFICATION FOR CAPACITORS
- 8.6.1 Benefits due to Released Generation Capacity
- 8.6.2 Benefits due to Released Transmission Capacity
- 8.6.3 Benefits due to Released Distribution Substation Capacity
- 8.6.4 Benefits due to Reduced Energy Losses
- 8.6.5 Benefits due to Reduced Voltage Drops
- 8.6.6 Benefits due to Released Feeder Capacity
- 8.6.7 Financial Benefits due to Voltage Improvement
- TABLE 8.3 Additional kWh Energy Increase After Capacitor Addition
- 8.6.8 Total Financial Benefits due to Capacitor Installations
- Example 8.19*
- TABLE 8.4 For Example 8.19
- 8.7 PRACTICAL PROCEDURE TO DETERMINE THE BEST CAPACITOR LOCATION
- 8.8 MATHEMATICAL PROCEDURE TO DETERMINE THE OPTIMUM CAPACITOR ALLOCATION
- FIGURE 8.21 Primary feeder with lumped-sum (or concentrated) and uniformly distributed loads and reactive current profile before adding the capacitor.
- 8.8.1 Loss Reduction due to Capacitor Allocation
- 8.8.1.1 Case 1: One Capacitor Bank
- FIGURE 8.22 Loss reduction with one capacitor bank.
- FIGURE 8.23 Loss reduction as a function of the capacitor-bank location and capacitor compensation ratio for a line segment with uniformly distributed loads (λ = 0).
- FIGURE 8.24 Loss reduction as a function of the capacitor-bank location and capacitor compensation ratio for a line segment with a combination of concentrated and uniformly distributed loads (λ = 1/4).
- FIGURE 8.25 Loss reduction as a function of the capacitor-bank location and capacitor compensation ratio for a line segment with a combination of concentrated and uniformly distributed loads (λ = 1/2).
- FIGURE 8.26 Loss reduction as a function of the capacitor-bank location and capacitor compensation ratio for a line segment with a combination of concentrated and uniformly distributed loads (λ = 3/4).
- FIGURE 8.27 Loss reduction as a function of the capacitor-bank location and capacitor compensation ratio for a line segment with concentrated loads (λ = 1).
- TABLE 8.5 Optimum Location and Optimum Loss Reduction
- FIGURE 8.28 Loss reduction due to a capacitor bank located at the optimum location on a line section with various combinations of concentrated and uniformly distributed loads.
- 8.8.1.2 Case 2: Two Capacitor Banks
- FIGURE 8.29 Loss reduction due to an optimum-sized capacitor bank located on a line segment with various combinations of concentrated and uniformly distributed loads.
- 8.8.1.3 Case 3: Three Capacitor Banks
- 8.8.1.4 Case 4: Four Capacitor Banks
- FIGURE 8.30 Loss reduction with two capacitor banks.
- 8.8.1.5 Case 5: n Capacitor Banks
- 8.8.2 Optimum Location of a Capacitor Bank
- FIGURE 8.31 Loss reduction with three capacitor banks.
- FIGURE 8.32 Loss reduction with four capacitor banks.
- FIGURE 8.33 Comparison of loss reduction obtainable from n = 1, 2, 3, and ∞ number of capacitor banks, with λ = 0.
- FIGURE 8.34 Comparison of loss reduction obtainable from n = 1, 2, 3, 4, and ∞ number of capacitor banks, with λ = 1/4.
- 8.8.3 Energy Loss Reduction due to Capacitors
- FIGURE 8.35 Relationship between the total capacitor compensation ratio and the reactive load factor for uniformly distributed load (λ = 0 and α = 1).
- FIGURE 8.36 Energy loss reduction with any capacitor-bank size, located at optimum location
- FIGURE 8.37 Energy loss reduction with any capacitor-bank size, located at the optimum location
- FIGURE 8.38 Energy loss reduction with any capacitor-bank size, located at the optimum location
- FIGURE 8.39 Energy loss reduction with any capacitor-bank size, located at the optimum location
- FIGURE 8.40 Energy loss reduction with any capacitor-bank size, located at the optimum location
- FIGURE 8.41 Effects of reactive load factors on energy loss reduction due to capacitor-bank installation on a line segment with uniformly distributed load (λ = 0).
- FIGURE 8.42 Effects of reactive load factors on energy loss reduction due to capacitor-bank installation on a line segment with a combination of concentrated and uniformly distributed loads (λ = 1/4).
- FIGURE 8.43 Effects of reactive load factors on energy loss reduction due to capacitor-bank installation on a line segment with a combination of concentrated and uniformly distributed loads (λ = 1/2).
- FIGURE 8.44 Effects of reactive load factors on loss reduction due to capacitor-bank installation on a line segment with a combination of concentrated and uniformly distributed loads (λ = 3/4).
- FIGURE 8.45 Effects of reactive load factors on energy loss reduction due to capacitor-bank installation on a line segment with a concentrated load (λ = 1).
- 8.8.4 Relative Ratings of Multiple Fixed Capacitors
- 8.8.5 General Savings Equation for Any Number of Fixed Capacitors
- 8.9 FURTHER THOUGHTS ON CAPACITORS AND IMPROVING POWER FACTORS
- FIGURE 8.46 Schematic diagram for the use of capacitors to reduce total line current by supplying reactive power locally: (a) without the use of capacitors and (b) with the use of capacitors.
- 8.10 CAPACITOR TANK–RUPTURE CONSIDERATIONS
- FIGURE 8.47 Time-to-rupture characteristics for 200 kvar 7.2 kV all-film capacitors.
- FIGURE 8.48 Capacitor reliability cycle.
- 8.11 DYNAMIC BEHAVIOR OF DISTRIBUTION SYSTEMS
- 8.11.1 Ferroresonance
- FIGURE 8.49 The LC circuit for ferroresonance.
- Example 8.20
- 8.11.2 Harmonics on Distribution Systems
- FIGURE 8.50 Harmonic analysis of peaked no-load current.
- FIGURE 8.51 Harmonic components of transformer exciting current.
- TABLE 8.6 The Influence of Three-Phase Transformer Connections on Third Harmonics
- FIGURE 8.52 Combinations of fundamental and third-harmonic waves: (a) harmonic in phase, (b) harmonic 90° leading, (c) harmonic in opposition, and (d) harmonic 90° lagging.
- PROBLEMS
- TABLE P8.5 Summary of Load Flows
- REFERENCES
- 9 Distribution System Voltage Regulation
- 9.1 BASIC DEFINITIONS
- 9.2 QUALITY OF SERVICE AND VOLTAGE STANDARDS
- FIGURE 9.1 Illustration of voltage spread on a radial primary feeder: (a) one-line diagram of a feeder circuit, (b) voltage profile at peak-load conditions, and (c) voltage profile at light-load conditions.
- TABLE 9.1 Typical Secondary Voltage Standards Applicable to Residential and Commercial Customers
- 9.3 VOLTAGE CONTROL
- 9.4 FEEDER VOLTAGE REGULATORS
- FIGURE 9.2 Typical single-phase 32-step pole-type voltage regulator used for 167 kVA or below.
- FIGURE 9.3 One-line diagram of a feeder, indicating the sequence of essential components.
- FIGURE 9.4 Typical platform-mounted voltage-regulators. (Siemens-Allis Company.)
- FIGURE 9.5 Individual feeder voltage regulation provided by a bank of distribution voltage regulators. (Siemens-Allis Company.)
- FIGURE 9.6 Regulator tap controls based on the set voltage, bandwidth, and time delay.
- FIGURE 9.7 Features of the control mechanism of a single-phase 32-step voltage regulator. (McGraw-Edison Company, Belleville, NJ.)
- FIGURE 9.8 Standard direct-drive tap changer used through 150 kV BIL, above 219 A.
- FIGURE 9.9 Four-step auto-booster regulators: (a) 50 A unit and (b) 100 A unit.
- 9.5 LINE-DROP COMPENSATION
- FIGURE 9.10 Simple schematic diagram and phasor diagram of the control circuit and line-drop compensator circuit of a step or induction voltage regulator.
- FIGURE 9.11 Determination of the voltage profiles for (a) peak loads and (b) light loads.
- Example 9.1
- FIGURE 9.12 The elements of a distribution substation for Example 9.1.
- TABLE 9.2 Overloading of Step-Type Feeder Regulators
- TABLE 9.3 Some Typical Single-Phase Regulator Sizes
- FIGURE 9.13 Feeder voltage profile.
- Example 9.2
- FIGURE 9.14 Voltage profile for Example 9.2.
- Example 9.3
- Example 9.4
- FIGURE 9.15 Feeder voltage profiles for zero load and for the annual peak load.
- TABLE 9.4 For Annual Peak Load
- TABLE 9.5 For Annual Peak Load
- Example 9.5
- TABLE 9.6 Actual Voltages vs. Voltage Criteria at Peak and Zero Loads
- TABLE 9.7 Values Obtained
- FIGURE 9.16 Voltage profiles.
- Example 9.6
- Example 9.7
- Example 9.8
- FIGURE 9.17 One-line diagram of a primary feeder supplying an industrial customer.
- Example 9.9
- FIGURE 9.18 Optimum location of a capacitor bank.
- FIGURE 9.19 Voltage profiles.
- Example 9.10
- 9.6 DISTRIBUTION CAPACITOR AUTOMATION
- FIGURE 9.20 A distribution capacitor automation algorithm switches capacitors on and off remotely and automatically, using voltage information from customer meters and var information from the substation.
- 9.7 VOLTAGE FLUCTUATIONS
- FIGURE 9.21 Permissible voltage-flicker-limit curve.
- FIGURE 9.22 Installation of series capacitor to reduce the flicker voltage caused by a fluctuating load.
- 9.7.1 Shortcut Method to Calculate the Voltage Dips due to a Single-Phase Motor Start
- Example 9.11
- 9.7.2 Shortcut Method to Calculate the Voltage Dips due to a Three-Phase Motor Start
- Example 9.12
- PROBLEMS
- FIGURE P9.10 Figure for Problem 9.10.
- TABLE P9.10 Table for Problem P9.10
- FIGURE P9.12 Figure for Problem 9.12.
- FIGURE P9.13 Figure for Problem 9.13.
- REFERENCES
- 10 Distribution System Protection
- 10.1 BASIC DEFINITIONS
- 10.2 OVERCURRENT PROTECTION DEVICES
- 10.2.1 Fuses
- FIGURE 10.1 Classification of high-voltage fuses.
- TABLE 10.1 Interrupting Ratings of Open-Fuse Cutouts
- FIGURE 10.2 Typical open-fuse cutout in pole-top style for 7.2/14.4 kV overhead distribution.
- FIGURE 10.3 Typical application of open-fuse cutouts in 7.2/14.4 kV overhead distribution.
- 10.2.2 Automatic Circuit Reclosers
- FIGURE 10.4 Typical fuse links used on outdoor distribution: (a) fuse link rated less than 10 A and (b) fuse link rated 10–100 A.
- FIGURE 10.5 Minimum-melting-TCC curves for typical (fast) fuse links. Curves are plotted to minimum test points, so all variations should be +20% in current.
- FIGURE 10.6 Typical transformer protection application of 34.5 kV SM-type power fuses.
- 10.2.3 Automatic Line Sectionalizers
- FIGURE 10.7 Feeder protection application of 34.5 kV SM-type power fuses.
- FIGURE 10.8 Cutaway view of typical 34.5 kV SM-type refill unit.
- TABLE 10.2 Asymmetrical Factors as Function of X/R Ratios
- FIGURE 10.9 Typical single-phase hydraulically controlled automatic circuit recloser: (a) type H, 4H, V4H, or L and (b) type D, E, 4E, or DV.
- FIGURE 10.10 Typical three-phase hydraulically controlled automatic circuit reclosers: (a) type 6H or V6H and (b) type RV, RVE, RX, RXE, etc.
- FIGURE 10.11 Typical three-pole automatic circuit recloser.
- FIGURE 10.12 Typical single- and three-phase automatic line sectionalizers: (a) type GH, (b) type GN3, (c) type GN3E, (d) type GV, (e) type GW, and (f) type GWC.
- 10.2.4 Automatic Circuit Breakers
- FIGURE 10.13 (a) and (b) Typical oil circuit breakers.
- FIGURE 10.14 Typical vacuum circuit breaker.
- FIGURE 10.15 A typical IAC single-phase overcurrent-relay unit.
- FIGURE 10.16 TCC of overcurrent relays.
- FIGURE 10.17 Time–current curves of IAC overcurrent relays with inverse characteristics.
- 10.3 OBJECTIVE OF DISTRIBUTION SYSTEM PROTECTION
- FIGURE 10.18 A distribution feeder protection scheme.
- 10.4 COORDINATION OF PROTECTIVE DEVICES
- 10.5 FUSE-TO-FUSE COORDINATION
- FIGURE 10.19 Coordinating fuses in series using TCC curves of the fuses connected in series.
- 10.6 RECLOSER-TO-RECLOSER COORDINATION
- TABLE 10.3 Coordination Table for GE Type “K” (Fast) Fuse Links Used in GE 50, 100, or 200 A Expulsion Fuse Cutouts and Connected in Series
- TABLE 10.4 Coordination Table for GE Type “T” (Slow) Fuse Links Used in GE 50, 100, or 200 A Expulsion Fuse Cutouts and Connected in Series
- 10.7 RECLOSER-TO-FUSE COORDINATION
- FIGURE 10.20 Typical recloser tripping characteristics.
- FIGURE 10.21 Recloser TCC curves superimposed on fuse TCC curves.
- FIGURE 10.22 Temperature cycle of fuse link during recloser operation.
- FIGURE 10.23 Recloser-to-fuse coordination (corrected for heating and cooling cycle).
- TABLE 10.5 Automatic Recloser and Fuse Ratings
- 10.8 RECLOSER TO SUBSTATION TRANSFORMER HIGH-SIDE FUSE COORDINATION
- 10.9 FUSE-TO CIRCUIT-BREAKER COORDINATION
- 10.10 RECLOSER-TO-CIRCUIT-BREAKER COORDINATION
- Example 10.1
- FIGURE 10.24 An example of recloser-to-relay coordination. Curve A represents TCCs of one instantaneous recloser opening. Curve B represents TCCs of one extended time-delay recloser opening. Curve C represents TCCs of the IAC relay.
- 10.11 FAULT-CURRENT CALCULATIONS*
- 10.11.1 Three-Phase Faults
- 10.11.2 Line-to-Line Faults
- 10.11.3 Single Line-to-Ground Faults
- TABLE 10.6 Estimated Values of the K0 Constant for Various Conditions
- 10.11.4 Components of the Associated Impedance to the Fault
- FIGURE 10.25 Typical pole-top overhead distribution circuit configuration.
- 10.11.5 Sequence-Impedance Tables for the Application of Symmetrical Components
- FIGURE 10.26 Various overhead pole-top conductor configurations: (a) without ground wire, z0 = z0,a; (b) with ground wire, z0 = z0,a + z′0; and (c) with ground wire, z0 = z0,a + z″0.
- FIGURE 10.27 Various overhead pole-top conductor configurations: (a) without ground wire, z0 = z0,a, (b) with ground wire, z0 = z0,a + z′0, and (c) with ground wire, z0 = z0,a + z″0.
- FIGURE 10.28 Various overhead pole-top conductor configurations with ground wire, z0 = z0,a + z′0.
- Example 10.2
- FIGURE 10.29 Various overhead pole-top conductor configurations: (a) without ground wire, z0 = z0,a and (b) with ground wire, z0 = z0,a + z′0
- FIGURE 10.30 Single-phase overhead pole-top configurations with ground wires: (a) z1φ = z′1φ and (b) z1φ = z″1φ.
- TABLE 10.7 Sequence-Impedance Values Associated with Figure 10.26, Ω/1000 ft
- TABLE 10.8 Sequence-Impedance Values Associated with Figure 10.27, Ω/1000 ft
- TABLE 10.9 Sequence-Impedance Values for Bare-Aluminum–Steel (AS) Associated with Figure 10.28, Ω/1000 ft
- TABLE 10.10 Sequence-Impedance Values for Bare-Aluminum–Steel (AS) Associated with Figure 10.29, Ω/1000 ft
- TABLE 10.11 Impedance Values Associated with Figure 10.30, Ω/1000 ft
- 10.12 FAULT-CURRENT CALCULATIONS IN PER UNITS
- Example 10.3
- TABLE 10.12 Fault-Current Formulas in Per Units
- FIGURE 10.31 A distribution substation.
- TABLE 10.13 Results of Example 10.3
- 10.13 SECONDARY-SYSTEM FAULT-CURRENT CALCULATIONS
- 10.13.1 Single-Phase 120/240 V Three-Wire Secondary Service
- FIGURE 10.32 A line-to-ground fault involving line l1 and neutral or line l2 and neutral.
- 10.13.2 Three-Phase 240/120 or 480/240 V Wye–Delta or Delta–Delta Four-Wire Secondary Service
- FIGURE 10.33 A wye–delta or delta–delta secondary service. If needed, the wye primary can be replaced with its equivalent delta, as illustrated.
- 10.13.3 Three-Phase 240/120 or 480/240 V Open-Wye Primary and Four-Wire Open-Delta Secondary Service
- FIGURE 10.34 An open-wye primary and open-delta secondary service.
- FIGURE 10.35 Various fault-current paths in the transformer and associated impedance-transfer ratios.
- 10.13.4 Three-Phase 208Y/120 V, 480Y/277 V, or 832Y/480 V Four-Wire Wye–Wye Secondary Service
- FIGURE 10.36 A three-phase wye–wye-connected four-wire secondary connection.
- Example 10.4
- FIGURE 10.37 A single-phase L–L secondary on a 120/240 V three-wire service.
- 10.14 HIGH-IMPEDANCE FAULTS
- 10.15 LIGHTNING PROTECTION
- 10.15.1 A Brief Review of Lightning Phenomenon
- FIGURE 10.38 An illustration of the lightning phenomenon.
- FIGURE 10.39 The complete process of a lightning flash.
- 10.15.2 Lightning Surges
- FIGURE 10.40 (a) Induced line charges due to indirect lightning strokes and (b) an occurence of a lightning among clouds.
- 10.15.3 Lightning Protection
- 10.15.4 Basic Lightning Impulse Level
- Example 10.5
- Example 10.6
- 10.15.5 Determining the Expected Number of Strikes on a Line
- FIGURE 10.41 The ground flash density of the United States.
- TABLE 10.14 Constant C for REA Standard Pole Lengths
- Example 10.7
- Example 10.8
- Example 10.9
- Example 10.10
- 10.16 INSULATORS
- PROBLEMS
- FIGURE P10.1 Distribution circuit of Problem 10.7.
- REFERENCES
- 11 Distribution System Reliability
- 11.1 BASIC DEFINITIONS
- 11.2 NATIONAL ELECTRIC RELIABILITY COUNCIL
- FIGURE 11.1 Regional Electric Reliability Councils.
- 11.3 APPROPRIATE LEVELS OF DISTRIBUTION RELIABILITY
- TABLE 11.1 Classification of Generic and Specific Causes of Outages
- FIGURE 11.2 Classification of reported outage events in the National Electric Reliability Study for the period July 1970–June 1979: (a) types of events, (b) generic subsystems, and (c) generic causes.
- FIGURE 11.3 Cumulative duration in minutes to restore reported customer outages.
- TABLE 11.2 Detailed Industrial Service Interruption Cost Example
- FIGURE 11.4 Cost versus system reliability.
- 11.4 BASIC RELIABILITY CONCEPTS AND MATHEMATICS
- 11.4.1 General Reliability Function
- FIGURE 11.5 A reliability planning procedure.
- FIGURE 11.6 The bathtub hazard function.
- FIGURE 11.7 Relationship between reliability and unreliability.
- 11.4.2 Basic Single-Component Concepts
- FIGURE 11.8 Two-state model.
- 11.5 SERIES SYSTEMS
- 11.5.1 Unrepairable Components in Series
- FIGURE 11.9 Block diagram of a series system with two components.
- FIGURE 11.10 Block diagram of a series system with n components.
- FIGURE 11.11 The reliability of a series system (structure) of n identical components.
- Example 11.1
- 11.5.2 Repairable Components in Series*
- 11.6 PARALLEL SYSTEMS
- 11.6.1 Unrepairable Components in Parallel
- FIGURE 11.12 Block diagram of a parallel system with two components.
- FIGURE 11.13 Block diagram of a parallel system with m components.
- 11.6.2 Repairable Components in Parallel*
- FIGURE 11.14 The reliability of a parallel system (structure) of n parallel components.
- Example 11.2
- FIGURE 11.15 A 4 mi long distribution express feeder.
- Example 11.3
- FIGURE 11.16 A primary system for Example 11.3.
- 11.7 SERIES AND PARALLEL COMBINATIONS
- FIGURE 11.17 A parallel–series system.
- FIGURE 11.18 A series–parallel system.
- Example 11.4
- FIGURE 11.19 Various combinations of block diagrams: (a) series, (b) parallel–series, (c) mixed parallel, (d) mixed parallel, and (e) series–parallel.
- Example 11.5
- Example 11.6
- FIGURE 11.20 System configuration.
- FIGURE 11.21 Imposed system configuration.
- TABLE 11.3 Summary of the Computations
- 11.8 MARKOV PROCESSES*
- FIGURE 11.22 Transition system (a) for a two-state system and (b) for a three-state system.
- Example 11.7
- FIGURE 11.23 Transition diagram.
- Example 11.8
- TABLE 11.4 Feeder Outage Data
- FIGURE 11.24 Transition diagram.
- 11.8.1 Chapman–Kolmogorov Equations
- Example 11.9
- 11.8.2 Classification of States in Markov Chains
- 11.9 DEVELOPMENT OF THE STATE-TRANSITION MODEL TO DETERMINE THE STEADY-STATE PROBABILITIES
- 11.10 DISTRIBUTION RELIABILITY INDICES
- 11.11 SUSTAINED INTERRUPTION INDICES
- 11.11.1 SAIFI
- 11.11.2 SAIDI
- 11.11.3 CAIDI
- 11.11.4 CTAIDI
- 11.11.5 CAIFI
- 11.11.6 ASAI
- 11.11.7 ASIFI
- 11.11.8 ASIDI
- 11.11.9 CEMIn
- 11.12 OTHER INDICES (MOMENTARY)
- 11.12.1 MAIFI
- 11.12.2 MAIFIE
- 11.12.3 CEMSMIn
- 11.13 LOAD- AND ENERGY-BASED INDICES
- 11.13.1 ENS
- 11.13.2 AENS
- 11.13.3 ACCI
- Example 11.10
- TABLE 11.5 Distribution System Data of GMEU Company
- TABLE 11.6 Annual Interruption Effects
- 11.14 USAGE OF RELIABILITY INDICES
- 11.15 BENEFITS OF RELIABILITY MODELING IN SYSTEM PERFORMANCE
- 11.16 ECONOMICS OF RELIABILITY ASSESSMENT
- PROBLEMS
- FIGURE P11.12 Various system configurations: (a) in series, (b) in series and parallel, (c) in parallel, and (d) in parallel and series, connections.
- FIGURE P11.13 Various system configurations: (a) series connections of number of combinations, and (b) the same as (a) but with different reliabilities.
- FIGURE P11.14 System configuration for Problem 11.14.
- TABLE P11.29A Distribution System Data
- TABLE P11.29B Annual Interruption Effects
- TABLE P11.30A Component Data for the Radial Feeder
- TABLE P11.30B Distribution System Data
- TABLE P11.30C Additional Distribution System Data
- REFERENCES
- 12 Electric Power Quality
- 12.1 BASIC DEFINITIONS
- 12.2 DEFINITION OF ELECTRIC POWER QUALITY
- 12.3 CLASSIFICATION OF POWER QUALITY
- TABLE 12.1 Classification of Electromagnetic Disturbances according to IEC
- 12.4 TYPES OF DISTURBANCES
- 12.4.1 Harmonic Distortion
- TABLE 12.2 Categories and Characteristics of Power System Electromagnetic Phenomena
- FIGURE 12.1 Various types of disturbances: (a) harmonic distortion, (b) noise, (c) notches, (d) sag, (e) swell, and (f) surge.
- TABLE 12.3 Sources and Characteristics of Surge Voltages in Primary and Secondary Distribution Circuits
- FIGURE 12.2 Various transients.
- 12.4.2 CBEMA and ITI Curves
- FIGURE 12.3 CBEMA curve.
- FIGURE 12.4 ITI curve.
- 12.5 MEASUREMENTS OF ELECTRIC POWER QUALITY
- 12.5.1 RMS Voltage and Current
- 12.5.2 Distribution Factors
- 12.5.3 Active (Real) and Reactive Power
- 12.5.4 Apparent Power
- 12.5.5 Power Factor
- 12.5.6 Current and Voltage Crest Factors
- Example 12.1
- 12.5.7 Telephone Interference and the I · T Product
- TABLE 12.4 Standard Telephone Interference Weighting Factors
- TABLE 12.5 IEEE Std. 519-1992 Limits for Harmonic Voltage Distortion in Percent at PCC
- Example 12.2
- Example 12.3
- 12.6 POWER IN PASSIVE ELEMENTS
- 12.6.1 Power in a Pure Resistance
- 12.6.2 Power in a Pure Inductance
- 12.6.3 Power in a Pure Capacitance
- 12.7 HARMONIC DISTORTION LIMITS
- 12.7.1 Voltage Distortion Limits
- 12.7.2 Current Distortion Limits
- FIGURE 12.5 Selection of PCC.
- TABLE 12.6 IEEE Std. 519-1992 Limits Imposed on Customers (120 V–69 kV) for Harmonic Current Distortion in Percent of IL for Odd Harmonic h at the PCC
- TABLE 12.7 IEEE Std. 519-1992 Limits Imposed on Customers (69–161 kV) for Harmonic Current Distortion in Percent of IL for Odd Harmonic h at the PCC
- TABLE 12.8 IEEE Std. 519-1992 Limits Imposed on Customers (above 161 kV) for Harmonic Current Distortion in Percent of IL for Odd Harmonic h at the PCC
- 12.8 EFFECTS OF HARMONICS
- TABLE 12.9 Comparison of Sensing Techniques for Various Waveforms
- 12.9 SOURCES OF HARMONICS
- FIGURE 12.6 Representation of a nonlinear load.
- FIGURE 12.7 General flow of harmonic currents in a radial power system: (a) without power capacitors and (b) with power capacitors.
- 12.10 DERATING TRANSFORMERS
- 12.10.1 K-Factor
- 12.10.2 Transformer Derating
- Example 12.4
- TABLE 12.10 Typical Values of Pec-r
- TABLE 12.11 The Results of Example 12.4, Part (a)
- 12.11 NEUTRAL CONDUCTOR OVERLOADING
- Example 12.5
- Example 12.6
- 12.12 CAPACITOR BANKS AND POWER FACTOR CORRECTION
- FIGURE 12.8 Power triangle for a PF correction capacitor bank.
- 12.13 SHORT-CIRCUIT CAPACITY OR MVA
- 12.14 SYSTEM RESPONSE CHARACTERISTICS
- 12.14.1 System Impedance
- 12.14.2 Capacitor Impedance
- 12.15 BUS VOLTAGE RISE AND RESONANCE
- FIGURE 12.9 Power system with shunt switched capacitor.
- Example 12.7
- 12.16 HARMONIC AMPLIFICATION
- FIGURE 12.10 Capacitor switching.
- Example 12.8
- 12.17 RESONANCE
- 12.17.1 Series Resonance
- FIGURE 12.11 Resonance circuits for (a) series resonance and (b) parallel resonance.
- Example 12.9
- 12.17.2 Parallel Resonance
- Example 12.10
- 12.17.3 Effects of Harmonics on the Resonance
- Example 12.11
- 12.17.4 Practical Examples of Resonance Circuits
- FIGURE 12.12 Practical examples of resonance circuits: (a) series resonance circuit, (b) its equivalent circuit, (c) parallel resonance circuit, and (d) its equivalent circuit.
- FIGURE 12.13 Parallel resonance considerations: (a) a parallel resonance prone system, (b) its equivalent circuit, (c) effects of capacitor sizes, and (d) effects of resistive loads.
- Example 12.12
- 12.18 HARMONIC CONTROL SOLUTIONS
- 12.18.1 Passive Filters
- FIGURE 12.14 Common passive filter configurations: (a) type I, (b) type II, (c) type III, and (d) type IV.
- FIGURE 12.15 A typical 480 V single-tuned wye- or delta-connected filter configurations.
- FIGURE 12.16 General procedure for designing individually tuned filter steps for harmonic control.
- Example 12.13
- TABLE 12.12 Harmonic Filter Design Spreadsheet for Example 12.13
- 12.18.2 Active Filters
- 12.19 HARMONIC FILTER DESIGN
- 12.19.1 Series-Tuned Filters
- Example 12.14
- Example 12.15
- 12.19.2 Second-Order Damped Filters
- Example 12.16
- Example 12.17
- 12.20 LOAD MODELING IN THE PRESENCE OF HARMONICS
- 12.20.1 Impedance in the Presence of Harmonics
- 12.20.2 Skin Effect
- 12.20.3 Load Models
- Example 12.18
- PROBLEMS
- TABLE P12.5 The Output of the Harmonic Analyzer
- REFERENCES
- 13 Distributed Generation and Renewable Energy
- 13.1 INTRODUCTION
- 13.2 RENEWABLE ENERGY
- 13.3 IMPACT OF DISPERSED STORAGE AND GENERATION
- 13.4 INTEGRATING RENEWABLES INTO POWER SYSTEMS
- FIGURE 13.1 Connecting DSGs into utility system.
- 13.5 DISTRIBUTED GENERATION
- 13.6 RENEWABLE ENERGY PENETRATION
- 13.7 ACTIVE DISTRIBUTION NETWORK
- 13.8 CONCEPT OF MICROGRID
- FIGURE 13.2 A typical microgrid connection scheme.
- 13.9 WIND ENERGY AND WIND ENERGY CONVERSION SYSTEM
- TABLE 13.1 Installed Wind Power Capacity Worldwide, as of 2009
- FIGURE 13.3 Solar and wind applications in the city of Kassel in the state of Hessen, Germany.
- FIGURE 13.4 Solar and wind turbine applications in the state of Rheinland-Pfalz in Germany.
- 13.9.1 Advantages and Disadvantages of Wind Energy Conversion Systems
- 13.9.2 Advantages of a Wind Energy Conversion System
- 13.9.3 Disadvantages of a Wind Energy Conversion System
- 13.9.4 Categories of Wind Turbines
- FIGURE 13.5 Horizontal-axis three-blade wind energy.
- FIGURE 13.6 Overview of differential types of wind energy converters.
- FIGURE 13.7 Eight categories of wind turbines used in the Altamont Pass in California.
- FIGURE 13.8 Major components of a horizontal-axis wind turbine.
- 13.9.5 Types of Generators Used in Wind Turbines
- FIGURE 13.9 Block diagram of a WECS: (a) using a dc generator, (b) using a synchronous alternator, and (c) using induction generator.
- FIGURE 13.10 Variable-speed pitch-regulated wind turbine.
- 13.9.6 Wind Turbine Operating Systems
- 13.9.6.1 Constant-Speed Wind Turbines
- 13.9.6.2 Variable-Speed Wind Turbines
- 13.9.7 Meteorology of Wind
- Example 13.1
- FIGURE 13.11 Pressure variations with altitude for US standard atmosphere.
- 13.9.7.1 Power in the Wind
- FIGURE 13.12 TSR diagrams for various types of wind energy converters. (The power coefficient gives a measure of how large a share of the wind’s power a turbine can utilize. The theoretical maximum of the value is 16/27 = 0.5926. The diagram shows the relation between TSR and power coefficient for different types of wind turbines: (a) windmill, (b) modern turbine with three blades, (c) vertical-axis Darrieus turbine, and (d) modern turbine with two blades.)
- Example 13.2
- 13.9.8 Effects of a Wind Force
- 13.9.9 Impact of Tower Height on Wind Power
- TABLE 13.2 Roughness Coefficient for Various Class Types of Terrain
- Example 13.3
- Example 13.4
- 13.9.10 Wind Measurements
- Example 13.5
- 13.9.11 Characteristics of a Wind Generator
- FIGURE 13.13 A typical power curve for a wind turbine.
- Example 13.6
- 13.9.12 Efficiency and Performance
- Example 13.7
- TABLE 13.3 Development of Wind Turbine Size, 1980–2005
- Example 13.8
- Example 13.9
- 13.9.13 Efficiency of a Wind Turbine
- 13.9.13.1 Generator Efficiency
- TABLE 13.4 Generator Efficiency
- TABLE 13.5 Relationship between Size and Efficiency
- 13.9.13.2 Gearbox
- 13.9.13.3 Overall Efficiency
- 13.9.13.4 Other Factors to Define the Efficiency
- Example 13.10
- 13.9.14 Grid Connection
- 13.9.15 Some Further Issues Related to Wind Energy
- 13.9.16 Development of Transmission System for Wind Energy in the United States
- 13.9.17 Energy Storage
- 13.9.18 Wind Power Forecasting
- 13.10 SOLAR ENERGY
- 13.10.1 Solar Energy Systems
- FIGURE 13.14 Wind and solar application in the city of Huleka in South Africa. (SMA Solar Technology AG.)
- FIGURE 13.15 Solar applications on the roof of Oregon State Capital, Salem, Oregon, United States. (SMA Solar Technology AG.)
- FIGURE 13.16 Solar installations at Montalto di Castro in Italy. (SMA Solar Technology AG.)
- FIGURE 13.17 Solar applications on the rooftop of a barn in Bayern, Germany. (SMA Solar Technology AG.)
- FIGURE 13.18 Solar module used in the city of Kassel in the state of Hessen, Germany. (SMA Solar Technology AG.)
- FIGURE 13.19 Solar and wind turbine applications in the state of Rheinland-Pfalz in Germany. (SMA Solar Technology AG.)
- 13.10.2 Crystalline Silicon
- FIGURE 13.20 Solar applications on a building in the city of Laatzen in the state of Niedersachsen, Germany. (SMA Solar Technology AG.)
- FIGURE 13.21 Solar applications in a sports stadium in the city of Mainz in the state of Rheinland-Pfalz in Germany. (SMA Solar Technology AG.)
- FIGURE 13.22 Solar application in a German school in San Salvador. (SMA Solar Technology AG.)
- FIGURE 13.23 Solar rooftop applications in the state of Baden-Wurttemberg, Germany. (SMA Solar Technology AG.)
- FIGURE 13.24 Typical 3 in. diameter cell.
- FIGURE 13.25 Typical I–V characteristic for a PV cell.
- Example 13.11
- Example 13.12
- Example 13.13
- Example 13.14
- Example 13.15
- Example 13.16
- 13.10.3 Effect of Sunlight on Solar Cell’s Performance
- TABLE 13.6 Latitudes of Selected Cities around the World
- Example 13.17
- FIGURE 13.26 Solution for Example 13.17.
- 13.10.4 Effects of Changing Strength of the Sun on a Solar Cell
- Example 13.18
- FIGURE 13.27 Variation of I–V characteristic of a solar cell due to changing power density.
- TABLE 13.7 Data for Example 13.19
- Example 13.19
- 13.10.5 Temperature’s Effect on Cell Characteristics
- Example 13.20
- 13.10.6 Efficiency of Solar Cells
- Example 13.21
- 13.10.7 Interconnection of Solar Cells
- Example 13.22
- FIGURE 13.28 Connection of 12 identical cells.
- FIGURE 13.29 Panel arrangement for Example 13.22.
- 13.10.8 Overall System Configuration
- FIGURE 13.30 Two fundamental solar generator configurations: (a) stand-alone system and (b) supplemental or cogeneration system.
- FIGURE 13.31 Solar module used in the city of Kassel in the state of Hessen, Germany. (SMA Solar Technology.)
- Example 13.23
- FIGURE 13.32 Installation of solar panels in Example 13.23.
- 13.10.9 Thin-Film PV
- 13.10.10 Concentrating PV
- 13.10.11 PV Balance of Systems
- 13.10.12 Types of Conversion Technologies
- FIGURE 13.33 Solar applications in a sports stadium in the city of Mainz in the state of Rheinland-Pfalz in Germany. (SMA Solar Technology AG.)
- FIGURE 13.34 Solar application in the INECO airport in the city of Valencia, Spain. (SMA Solar Technology AG.)
- 13.10.13 Linear CSP Systems
- 13.10.14 Power Tower CSP Systems
- 13.10.15 Dish/Engine CSP Systems
- 13.10.16 PV Applications
- 13.10.16.1 Utility-Interactive PV Systems
- 13.10.16.2 Stand-Alone PV Systems
- PROBLEMS
- TABLE P17.1 Necessary Energy Data for the Cottage
- REFERENCES
- GENERAL REFERENCES
- 14 Energy Storage Systems for Electric Power Utility Systems
- 14.1 INTRODUCTION*
- 14.2 STORAGE SYSTEMS
- 14.3 STORAGE DEVICES
- FIGURE 14.1 Comparison of storage technologies.
- 14.3.1 Large Hydro
- 14.3.2 Compressed Air Storage
- 14.3.3 Pumped Hydro
- 14.3.4 Hydrogen
- 14.3.5 High-Power Flywheels
- 14.3.6 High-Power Flow Batteries
- 14.3.7 High-Power Supercapacitors
- 14.3.8 Super Conducting Magnetic Energy Storage
- 14.3.9 Heat or Cold Storage
- FIGURE 14.2 SMES unit with double GTO thyristor bridge.
- 14.4 BATTERY TYPES
- 14.4.1 Secondary Batteries
- FIGURE 14.3 The trend of exponential improvement in battery performance.
- 14.4.2 Sodium–Sulfur Batteries
- 14.4.3 Flow Battery Technology
- 14.4.3.1 Zinc–Bromine Flow Battery
- 14.4.3.2 Vanadium Redox Flow Battery
- 14.4.4 Lithium-Ion Batteries
- 14.4.4.1 Lithium–Titanate Batteries
- 14.4.4.2 Lithium Ion Phosphate Batteries
- 14.4.5 Lead–Acid Batteries
- 14.4.5.1 Advanced Lead–Acid Batteries
- 14.4.6 Nickel–Cadmium Batteries
- 14.5 OPERATIONAL PROBLEMS IN BATTERY USAGE
- 14.6 FUEL CELLS
- FIGURE 14.4 A block diagram of a fuel cell system.
- FIGURE 14.5 Flows and reactions in a fuel cell.
- 14.6.1 Types of Fuel Cells
- 14.6.1.1 Polymer Electrolyte Membrane
- TABLE 14.1 Brief Comparison of Five Fuel Cell Technologies
- 14.6.1.2 Phosphoric Acid Fuel Cell
- 14.6.1.3 Molten Carbonate Fuel Cell
- 14.6.1.4 Solid Oxide Fuel Cell
- REFERENCES
- 15 Concept of Smart Grid and Its Applications
- 15.1 BASIC DEFINITIONS
- 15.2 INTRODUCTION
- FIGURE 15.1 The conceptual representation of the smart grid network framework of NIST.
- FIGURE 15.2 The representation of a smart grid as a tree.
- 15.3 NEED FOR ESTABLISHMENT OF SMART GRID
- FIGURE 15.3 Legacy systems (today’s electric grid).
- FIGURE 15.4 2007 electric generation by source.
- TABLE 15.1 Comparison of the Features of the Smart Grid with the Existing Grid
- FIGURE 15.5 Solar and wind applications in the city of Kassel in the state of Hessen, Germany. (SMA Solar Technology AG.)
- FIGURE 15.6 Solar and wind turbine applications in the state of Rheinland-Pfalz in Germany. (SMA Solar Technology AG.)
- FIGURE 15.7 Solar installations in Germany. (SMA Solar Technology AG.)
- FIGURE 15.8 Solar applications on the roof of Munich Temple in Germany. (SMA Solar Technology AG.)
- FIGURE 15.9 Solar application in the city of Kassel in the state of Hessen in Germany. (SMA Solar Technology AG.)
- 15.4 SMART GRID APPLICATIONS VERSUS BUSINESS OBJECTIVES
- Example 15.1
- Example 15.2
- Example 15.3
- 15.5 ROOTS OF THE MOTIVATION FOR THE SMART GRID
- TABLE 15.2 Enabled Applications
- TABLE 15.3 Smart Grid Applications
- FIGURE 15.10 Application of Ethernet TCP/IP sensors, transducers, and communication protocol for load control.
- 15.6 DISTRIBUTION AUTOMATION
- FIGURE 15.11 Tasks involved in the distribution level automation (at the MV level).
- FIGURE 15.12 The tasks involved in the distribution system monitoring.
- FIGURE 15.13 The tasks of an AMI.
- FIGURE 15.14 An illustration for how to control volt/var flows related to a distribution primary line using the individual, independent, stand-alone volt/var regulating equipment under the traditional VVC approach.
- 15.7 ACTIVE DISTRIBUTION NETWORKS
- FIGURE 15.15 Solar applications in Bruchweg stadium- FSV Mainz 05, Germany. (SMA Solar Technology AG.)
- FIGURE 15.16 Solar applications in the state of Crevillente in Spain. (SMA Solar Technology AG.)
- FIGURE 15.17 Solar applications in Montalto di Castro in Italy. (SMA Solar Technology AG.)
- 15.8 INTEGRATION OF SMART GRID WITH DISTRIBUTION MANAGEMENT SYSTEM
- FIGURE 15.18 Integration of the existing DMS with smart grid.
- 15.9 VOLT/VAR CONTROL IN DISTRIBUTION NETWORKS
- 15.9.1 Traditional Approach to Volt/VAR Control in the Distribution Networks
- Example 15.4
- 15.9.2 SCADA Approach to Control Volt/VAR in the Distribution Networks
- Example 15.5
- FIGURE 15.19 Var dispatch components of a SCADA system.
- FIGURE 15.20 Var dispatch rules applied (and no action is required).
- FIGURE 15.21 The capacitor bank is switched on.
- FIGURE 15.22 Change in reactive power is detected, and the capacitor bank is switched off.
- 15.9.3 Integrated Volt/VAR Control Optimization
- Example 15.6
- FIGURE 15.23 VVO system configuration.
- 15.10 EXISTING ELECTRIC POWER GRID
- 15.11 SUPERVISORY CONTROL AND DATA ACQUISITION
- FIGURE 15.24 SCADA.
- 15.12 ADVANCED SCADA CONCEPTS
- FIGURE 15.25 SCADA in a virtual system established by a WAN.
- 15.12.1 Substation Controllers
- 15.13 ADVANCED DEVELOPMENTS FOR INTEGRATED SUBSTATION AUTOMATION
- FIGURE 15.26 Substation controller.
- FIGURE 15.27 Configuration of SA system.
- 15.14 EVOLUTION OF SMART GRID
- FIGURE 15.28 The evolution of smart grid as a function of return-on-investment versus time.
- FIGURE 15.29 Return on investments for a smart grid.
- FIGURE 15.30 The additional steps that are necessary to achieve the VVO.
- 15.15 SMART MICROGRIDS
- FIGURE 15.31 The dc and ac schematics of an MRG energy DG system.
- FIGURE 15.32 The ac schematics of an MRG energy DG system.
- 15.16 TOPOLOGY OF A MICROGRID
- FIGURE 15.33 The topology of a smart microgrid with required microgrid components.
- 15.17 FUTURE OF A SMART GRID
- FIGURE 15.34 The envisioned smart grid of the future.
- 15.18 STANDARDS OF SMART GRIDS
- FIGURE 15.35 Development of standards for the smart grid.
- FIGURE 15.36 The application of IEC 61850 and CIM to a substation environment.
- FIGURE 15.37 Developing the CIM for distribution applications as well as its application to the field operations.
- 15.19 ASSET MANAGEMENT
- FIGURE 15.38 The IEC 61968 IRM showing activity diagrams and sequence diagrams that are organized by the IRM.
- 15.20 EXISTING CHALLENGES TO THE APPLICATION OF THE CONCEPT OF SMART GRIDS
- 15.21 EVOLUTION OF SMART GRID
- FIGURE 15.39 Illustrates the possible future application of the smart grid concept at the substation level as well as between substations.
- FIGURE 15.40 Present and future research areas in smart grid applications.
- REFERENCES
- Back Matter
- Appendix A: Impedance Tables for Lines, Transformers, and Underground Cables
- TABLE A.1 Characteristics of Copper Conductors, Hard-Drawn, 97.3% Conductivity
- TABLE A.2 Characteristics of Anaconda Hollow Copper Conductors
- TABLE A.3 Characteristics of General Cable Type HH Hollow Copper Conductors
- TABLE A.4 Characteristics of Alcoa Aluminum Conductors, Hard-Drawn, 61% Conductivity
- TABLE A.5 Characteristics of Aluminum Cable, Steel Reinforced (Aluminum Company of America)
- TABLE A.6 Characteristics of “Expanded” Aluminum Cable, Steel Reinforced (Aluminum Company of America)
- TABLE A.7 Characteristics of Copperweld Copper Conductors
- TABLE A.8 Characteristics of Copperweld Conductors
- TABLE A.9 Electrical Characteristics of Overhead Ground Wires
- TABLE A.10 Inductive Reactance Spacing Factor Xd, Ω/(Conductor mi), at 60 Hz
- TABLE A.11 Zero-Sequence Resistive and Inductive Factors Ω/(Conductor · mi)
- TABLE A.12 Shunt Capacitive Reactance Spacing Factor x′d (MΩ/Conductor · mi), at 60 Hz
- TABLE A.13 Zero-Sequence Shunt Capacitive Reactance Factor x′0, MΩ/(Conductor · mi)
- TABLE A.14 Standard Impedances of Distribution Transformers
- TABLE A.15 Standard Impedances for Power Transformers 10,000 kVA and below
- TABLE A.16 Standard Impedance Limits for Power Transformers Above 10,000 kVA
- TABLE A.17 60 Hz Characteristics of Three-Conductor Belted Paper-Insulated Cables
- TABLE A.18 60 Hz Characteristics of Three-Conductor Shielded Paper-Insulated Cables
- TABLE A.19 60 Hz Characteristics of Three-Conductor Oil-Filled Paper-Insulated Cables
- TABLE A.20 60 Hz Characteristics of Single-Conductor Concentric-Strand Paper-Insulated Cables
- TABLE A.21 60 Hz Characteristics of Single-Conductor Oil-Filled (Hollow-Core) Paper-Insulated Cables
- TABLE A.22 Current-Carrying Capacity of Three-Conductor Belted Paper-Insulated Cables
- TABLE A.23 Current-Carrying Capacity of Three-Conductor Shielded Paper-Insulated Cables
- TABLE A.24 Current-Carrying Capacity of Single-Conductor Solid Paper-Insulated Cables
- TABLE A.25 60 Hz Characteristics of Self-Supporting Rubber-Insulated Neoprene-Jacketed Aerial Cable
- REFERENCES
- Appendix B: Graphic Symbols Used in Distribution System Design
- TABLE B.1 Graphic Symbols Used in Distribution System Design
- Appendix C: Standard Device Numbers Used in Protection Systems
- Appendix D: The Per-Unit System
- D.1 INTRODUCTION
- D.2 SINGLE-PHASE SYSTEM
- Example D.1
- Example D.2
- D.3 CONVERTING FROM PER-UNIT VALUES TO PHYSICAL VALUES
- D.4 CHANGE OF BASE
- Example D.3
- D.5 THREE-PHASE SYSTEMS
- Example D.4
- Example D.5
- Example D.6
- Example D.7
- TABLE D.1 Results of Example D.7
- PROBLEMS
- Appendix E: Glossary for Distribution System Terminology
- REFERENCES
- Notation
- Answers to Selected Problems
- Chapter 2
- Chapter 3
- Chapter 4
- Chapter 5
- Chapter 6
- Chapter 7
- Chapter 8
- Chapter 9
- Chapter 10
- Chapter 11
- Index
People Also Search:
electric power distribution engineering
electric power distribution engineering 3rd gonen
electric power distribution engineering 3rd solution manual download pdf
electric power distribution engineering 3rd download scribd
electric power distribution engineering 3rd